How it works
Power factor is the ratio of real power to apparent power, P/(V_rms·I_rms). For a sinusoidal current it is simply cos φ, the cosine of the phase angle between voltage and current. Most power-electronic loads draw a distorted current instead, and then the power factor has two parts. With a sinusoidal line voltage, only the fundamental component of the current carries real power, so P = V·I₁·cos φ₁. The harmonics add to the RMS current without adding power. That splits the power factor into the displacement factor cos φ₁ and the distortion factor I₁/I_rms = 1/√(1 + THD²), and the true power factor is their product.
This is why a capacitor-input rectifier can have a fundamental almost exactly in phase with the voltage and still a power factor of only about 0.6: its current pulses contain large third, fifth and seventh harmonics. The distortion factor, not the phase angle, does the damage. It also explains why measuring cos φ with a meter that only looks at the fundamental can give a reassuring number for a load that is in fact drawing far more RMS current than its power suggests.
IEC 61000-3-2 limits the harmonic currents that equipment connected to the public low-voltage grid may draw, for products with up to 16 A per phase. Equipment is divided into classes. Class A covers most equipment and has fixed limits in amperes. Class D covers personal computers, monitors and television receivers from 75 to 600 W, and its limits are set per watt of input power, which makes them much stricter for small loads. The page compares each harmonic you enter with the selected class and shows how far it is over or under.
The harmonic percentages have to come from somewhere: a power analyzer, an oscilloscope with an FFT, or a simulation such as the line-cycle simulation on the bulk-capacitor page. The calculator does not estimate them from the circuit; it turns a spectrum into power factor figures and a limit check.
Design procedure
- 1Measure or simulate the input current at the operating point you need to assess, usually full load and nominal voltage.
- 2Enter the fundamental current, its phase angle and the harmonic percentages.
- 3Read the true power factor and RMS current, and use the RMS value to size fuses, filters and wiring.
- 4Select the class that applies to the product and check each harmonic against the limit.
- 5If harmonics exceed the limits, consider passive PFC, a valley-fill circuit or an active PFC boost stage, then measure again with a compliant analyzer.
Formulas
- Current THD
- THD = √(Σ I_n²)/I₁
- RMS current
- I_rms = I₁·√(1 + THD²)
- Real power (sinusoidal voltage)
- P = V_rms·I₁·cos φ₁
- Power factor
- PF = P/(V_rms·I_rms) = cos φ₁ · 1/√(1 + THD²)
- Class D limit
- I_n,max = (mA/W)_n · P, 3: 3.4, 5: 1.9, 7: 1.0, 9: 0.5, 11: 0.35, 13–39: 3.85/n, not above the Class A value
Worked example
The defaults describe a small capacitor-input power supply with no power factor correction on a 230 V line: 0.5 A of fundamental current, 5° displacement, and harmonic currents of 85, 62, 38, 18, 7, 6 and 5 % for orders 3 to 15. These percentages are a representative spectrum for this kind of rectifier, not a measurement of a particular product. The current THD is 114 %, so although the displacement factor is 0.996, the distortion factor is only 0.660 and the true power factor is 0.658. The load takes 115 W but draws 0.76 A rms, an apparent power of 174 VA. Against the Class A limits every harmonic passes, because they are fixed amperes intended for larger equipment. As a Class D product at 115 W, however, the 3rd harmonic of 425 mA exceeds its 390 mA limit and the 5th, 7th and 9th are 42 %, 66 % and 57 % over. This is the situation that pushes PC power supplies above 75 W toward active PFC or at least a valley-fill or passive PFC stage. The power factor values were checked against a separate Python program that synthesizes the waveform with random harmonic phases and computes P and I_rms numerically.
Common mistakes
- Quoting cos φ as the power factor for a rectifier load, which ignores the distortion factor.
- Sizing fuses and wiring from the real power and nominal voltage instead of the RMS current.
- Assuming Class A limits apply to a PC, monitor or TV supply above 75 W, which falls under Class D.
- Treating harmonic limits from summaries as a compliance result instead of checking the current standard and test conditions.
- Using a harmonic spectrum measured on a stiff laboratory source when the product will run from a soft line, which changes the spectrum.
Frequently asked questions
Why is the power factor low when the current is in phase with the voltage?
Because harmonics raise the RMS current without carrying real power. A capacitor-input rectifier draws narrow pulses centred on the voltage peak, so the fundamental is nearly in phase, but the large 3rd, 5th and 7th harmonics make the RMS current much larger than the fundamental. The distortion factor 1/√(1 + THD²) then limits the power factor.
Does the phase of each harmonic matter?
Not for the power factor, as long as the voltage is sinusoidal: harmonics of a different frequency from the voltage carry no average power whatever their phase, and they add to the RMS value as a root sum of squares. The harmonic phases do change the shape of the waveform and its peak current, which is why the verification uses random phases.
Are the limit values here authoritative?
They follow the IEC 61000-3-2 tables as reproduced in summaries of the standard, and we checked them against more than one such source. They are not taken from the current edition of the standard itself. For a compliance decision, use the current consolidated edition, which also defines measurement conditions, averaging and which class applies to your product.
What about Class B and Class C?
Class B covers portable tools and allows 1.5 times the Class A limits. Class C covers lighting equipment and has its own limits, partly relative to the fundamental and partly per watt, with special rules for low power. They are not included in this calculator.
How were the numbers checked?
A separate Python program synthesizes one line cycle from the fundamental and the harmonics with random phases, computes the real power as the average of v·i and the RMS values from the samples, and its power factor, real power and RMS current match the calculator. The limit functions were checked at several orders against the formulas in the references.
References
- IEC 61000-3-2, "Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits for harmonic current emissions (equipment input current ≤ 16 A per phase)" (equipment classes and harmonic limits; the current consolidated edition is 5.1, 2020).
- N. Mohan, T. M. Undeland, W. P. Robbins, "Power Electronics: Converters, Applications, and Design", chapter on line-frequency diode rectifiers (displacement and distortion factors, THD of capacitor-input rectifiers).
- The power factor values on this page were recomputed independently in Python from synthesized waveforms.
Results are engineering estimates. Verify your design with datasheets, simulation and measurement.